This worksheet runs and records a cleanroom recovery time test using the 100:1 method: challenge the room with particles, stop the challenge, and measure the time for the concentration to fall to one-hundredth of the challenge value. It applies to non-unidirectional (turbulently ventilated) rooms; a true Grade A unidirectional zone demonstrates continuous sweep instead (see airflow velocity testing). Replace every <<FILL: ...>> placeholder and set your own acceptance target with a documented justification. A worked example and a filled specimen follow. This content is educational and general; confirm the method against ISO 14644-3 before you rely on it.
Step 1: define the test basis
Step 2: generate and confirm the challenge
- Introduce the aerosol challenge at the defined location(s) with the HVAC running normally.
- Confirm with the counter that the concentration reached approximately the target challenge value before stopping the challenge.
- Record the actual peak challenge concentration achieved.
Step 3: log the decay
Log concentration at regular intervals from the moment the challenge stops. Add rows as needed.
Step 4: determine the recovery time
Step 5: downstream use of this result
State where this measured recovery time is used operationally, so the number has a documented purpose rather than sitting unused in a file.
Step 6: sign-off
References
ISO 14644-3:2019, Cleanrooms and associated controlled environments, Part 3: Test methods (recovery test, described in original wording here; refer to the standard for its exact procedure).
EU GMP Annex 1 (2022), for the expectation that recovery time be demonstrated for non-unidirectional cleanrooms and used to support operational claims.
Confirm the current version of each standard before issue.
Worked example
Challenge a Grade C room to 35,200,000 particles/m3 at the considered size, about 10 times the ISO 8 in-operation limit of 3,520,000/m3. The 1/100 pass threshold is 352,000/m3.
The concentration first drops below 352,000/m3 at 14 minutes and stays below it afterward. Measured recovery time: 14 minutes. Against an acceptance target of 20 minutes or less (justified by the site’s changeover procedure), the room passes, and 14 minutes is recorded as the qualified recovery time, used downstream to set a 20-minute post-exit settle period before the room is declared at rest.
Filled specimen
Common inspection findings this worksheet prevents
- Recovery time never measured for a non-unidirectional room, leaving the at-rest definition and changeover hold time with no supporting data.
- An acceptance target copied from another firm’s published number (commonly 15 or 20 minutes) with no justification tied to this room’s own operational claims.
- The challenge concentration not confirmed against the target before stopping, so the 1/100 threshold calculation is built on an assumed, not measured, starting point.
- A measured recovery time that is never fed into any actual procedure (settle period, changeover, re-entry criterion), so the test exists only on paper.
How to adapt this worksheet
- Set your room’s grade, considered particle size, and class limit from your own classification basis.
- Confirm your challenge generation equipment and counter are calibrated and appropriate for the concentrations involved.
- Set your own acceptance target and write down the operational basis for it in Step 1, rather than copying a commonly cited number.
- Complete Step 5 for every test; a recovery time with no stated downstream use is a gap an inspector will find.